How to calculate
Multiply the population by per-person use. Add other daily use and apply the allowance. Multiply average demand by each peaking factor, then convert the peak-hour equivalent rate to liters per second and cubic meters per hour.
Worked example
Use Service population 1000 · Average household use (L per person per day) 225 · Other average demand (L/day) 0 · Additional allowance on base demand (%) 10 · Maximum-day multiplier on average demand 1.4 · Peak-hour multiplier on average rate 2.3. The result is ≈ 247.5 m³/day.
Input and result notes
The editable examples illustrate a planning estimate. Set use rates and factors for the site and jurisdiction. Add other demand explicitly when it is separate from the per-person rate.
City of Winnipeg water demand estimation and design guidelines