How to calculate
For a straight pull, multiply the largest raceway trade size by eight. For each angle, U-pull, or splice row, multiply its largest entry by six and add the other entries in the row. Use the largest requirement in each direction.
Worked example
Use Largest horizontal straight-pull raceway trade size (in) 2 · Largest vertical straight-pull raceway trade size (in) 1.5 · Angle, U-pull or splice rows as side | comma-separated trade sizes top | 2, 1.5. The result is 16 in × 13.5 in.
Input and result notes
Enter one row for each set of entries on a side. Side means left, right, top, or bottom. Use trade sizes, such as 1.5. This calculation covers standard side-wall entries with conductors 4 AWG or larger. Verify same-conductor raceway separation, listed exceptions, entries opposite a removable cover, depth, and local adoption separately.