How to calculate
Add the allowance for all countable conductors and two units per device yoke or gang. Add clamp and support allowances where applicable. The first four entering grounds share one allowance of the largest size, with one-quarter per additional ground.
Worked example
Use AWG | conductor units | yokes or gangs | entering grounds 14 | 4 | 1 | 2 / 12 | 2 | 0 | 3 · Standard internal cable clamp present No · Luminaire support stud present No · Hickey support fitting present No. The result is 19.3125 in³.
Input and result notes
Enter the code-counted units for each wire size. Conductors spliced, terminated, or passing through count once. A qualifying long unbroken loop counts twice. A pigtail that stays entirely inside the box does not count. Assign each device gang to its largest connected conductor. Special assemblies and isolated grounding arrangements may have additional rules. Check the locally adopted edition.