Box Fill Calculator

Calculate minimum electrical box fill volume for 18 through 6 AWG under 2023 NEC 314.16. Compare it to the box’s marked volume.

This checks only the entered volume allowances under the 2023 NEC. Confirm the locally adopted code, conductor counts, fittings, and special conditions with a qualified electrician before selecting a box.

Result
—

How to calculate

Add the allowance for all countable conductors and two units per device yoke or gang. Add clamp and support allowances where applicable. The first four entering grounds share one allowance of the largest size, with one-quarter per additional ground.

Worked example

Use AWG | conductor units | yokes or gangs | entering grounds 14 | 4 | 1 | 2 / 12 | 2 | 0 | 3 · Standard internal cable clamp present No · Luminaire support stud present No · Hickey support fitting present No. The result is 19.3125 in³.

Input and result notes

Enter the code-counted units for each wire size. Conductors spliced, terminated, or passing through count once. A qualifying long unbroken loop counts twice. A pigtail that stays entirely inside the box does not count. Assign each device gang to its largest connected conductor. Special assemblies and isolated grounding arrangements may have additional rules. Check the locally adopted edition.